Close window

Brightness Transmitter

Part number: 7.1414.40.xxx

  • Description

    7.1414.40.102
    The instrument serves for the acquisition of the illumination intensity of the daylight.

    • angle-independent
    The electrical output can be used for the control of shading devices, heating systems, and
    irrigation plants. The acquisition is carried out in the upper part (dome) of the instrument. The acquisition angle is ±90 degree.
    The model with „heating“ avoids a possible dewing on the dome.
  • Specification

    Brightness
    Spectral range
    350 ... 820 nm
    Accuracy
    ±2 % of calibration standard
    Acquisition angle elevation
    0 ... 90 °
    Acquisition angle azimut
    0 ... 360 °
    Operating voltage
    Electronic
    15 ... 24 V DC or
    24 V AC
    Heating
    24 V AC/­DC, 300 mA
    General
    Ambient temp.
    -30 ... +70 °C
    Electr. connection
    clamp connection,
    screwed cable gland
    Protection
    IP 65
    Dimension
    80 x 82 x 112 mm
    Weight
    0.15 kg
  • Versions

     
    7.1414.40.102
    Product number 7.1414.40.102
    Brightness
    Measuring range
    0 ... 100 kLux
    Electrical output
    0 ... 10 V
    Product number 7.1414.40.112
    Brightness
    Measuring range
    0 ... 10 kLux
    Electrical output
    0 ... 10 V
    Product number 7.1414.40.141
    Brightness
    Measuring range
    0 ... 1 kLux
    Electrical output
    4 ... 20 mA
    Product number 7.1414.40.152
    Brightness
    Measuring range
    0 ... 5 kLux
    Electrical output
    0 ... 10 V
  • Accessories

    Product
    Product name
    Product name / Brief description
    4.3185.xx.009

    Hanger 1 m ( for radiation sensors )

    4.3185.xx.009

    Hanger 1 m ( for radiation sensors )


    The hanger is used for laterally mounting of a radiation- or brightness transmitter onto a mast.
     
    General
    Length
    1 m
    Material
    Aluminium
    Tube diameter
    Ø 50 mm
    Weight
    1.8 kg
    506345

    Adapter Compact

    506345

    Adapter Compact


    The adapter serves for mounting a radiation transmitter, baro transmitter or brightness transmitter onto a traverse (4.3171.30.000, 4.3171.40.000) or holder (506 347).
     
    General
    Material
    Aluminium, anodized
    Dimension
    100 x 115 x 65 mm
    Weight
    0.5 kg
    508805

    Adapter Compact 0 ... 90 ° adjustable

    508850

    Adapter Compact 0 ... 90 ° adjustable


    The adapter serves for mounting a radiation transmitter, baro transmitter or brightness transmitter onto a traverse (4.3171.30.000, 4.3171.40.000) or holder (506 347).
     
    General
    Material
    Aluminium, anodized
    Dimension
    100 x 115 x 65 mm
    Weight
    0.5 kg
    Function
    0 ... 90 ° adjustable
  • Further information